Function
Streamer’s Pathfinder 360 ALPHA (P360A) is pole mounted fault indicator. It is intended on the distribution lines up to 66 kV. The P360A helps to locate the faults phase to phase or phase to ground on the line with 2 very bright LEDs and therefore sensibly reduces the downtimes.
Operation principle
Streamer’s P360A Fault Indicators sense out of balance electromagnetic fields in a single or 3 phases high voltage network. Sensing is triggered when it detects fault current, above the current/time threshold curve, passing in the line conductors.
Streamer’s P360A will indicate the fault by lighting a bright LED and by sending the information by SMS/data to a cell phone or directly to a server.
Technical characteristics
P360 Alpha | P360 AC | |
APPLICATION | Permanent | Permanent |
INSTALLATION | On Pole (Wooden, Metal, Concrete) | On Pole (Wooden, Metal, Concrete) |
OPERATING VOLTAGE | <66 kV | <66 kV |
CURRENT TRIPPING |
Sensitive Earth Fault 4 A Normal Min 12 A |
Sensitive Earth Fault 4 A Normal Min 12 A |
RESPONSE TIME | Min 20 | Min 20 |
INDICATION | 2 very bright LEDs | 2 very bright LEDs |
VISIBILITY | 100 m daytime | 100 m daytime |
FAULT DETECTED | ||
P-P | + | + |
P-G | + | + |
DIFFERENCE TRANSIENT/ PERMANENT FAULT |
All types, except type "S" | All types, except type "S" |
RESET |
After timer Manuel w Magnet Return of Voltage |
After timer Manuel w Magnet Return of Voltage |
TEST | With Magnet | With Magnet |
LIVE LINE INSTALLATION | + | + |
BATTERY LIFE | 10 years | 10 years |
TEMPERATURE | -50°C to +80°C | -50°C to +80°C |
PROTECTION CLASS | IP67 | IP67 |
EMI |
BS EN 50081 -1 BS EN 50082 -2 IEC 801-2 -3 -4 |
BS EN 50081 -1 BS EN 50082 -2 IEC 801-2 -3 -4 |
Fault Indication
P360A (D, S, or F &FD) | via LED |
P360A COM GSM | via LED, SMS service |
P360A COM GPRS | via LED, GPRS |
P360A ROSCO |
via LED, analog output |
Integration
Pathfinder can be directly integrated in the existing SCADA System.
Standards
ELECTROMAGNETIC COMPATIBILITY
The PATHFINDER 360 ALPHA has been fully EMC tested to the following standards:
BS EN 50081-1: 1992 Generic emissions standard (Heavy industrial) – none detected
BS EN 50082-2: 1992 Generic immunity standard (Heavy industrial)
IEC 801-2: 1991 Electrostatic discharge
IEC 801-3: 1984 Radiated electromagnetic fields
IEC 801-4: 1988 Fast transient/Bursts
BS EN 60068: Environmental
IEC 60943: 1998 Temperature tests
BS EN 60068: Vibration endurance testing
BS EN 60068: Impact testing
Pathfinder casing chemical resistance
Impact testing – Airgun tests
Reference Numbers
Fault indicator P360A | FO.P3.PL30.00.WW |
Fault indicator P360A ROSCO | FO.P3.PL3T.00.WW |
Fault indicator P360A COM GSM | FO.P3.PL3G.00.WW |
Fault indicator P360A COM GPRS | FO.P3.PL3P.00.WW |